Highlights

MSA pre-programs the ProtoCarrier solution and maps each device to support the various protocols and configurations, including BACnet MS/TP, BACnet/IP, Modbus TCP/IP, LonWorks, and many others. No software or configuration files are required to install the device in the field.

1. MSA GRID SUPPORT
  • Register your ProtoCarrier to the MSA Grid interface for remote access to local applications, configuration, and device management
2. RAPID TIME-TO-MARKET
  • Plug-and-play solution to OEM device for rapid deployment without having to redesign the hardware
3. SERIAL, ETHERNET, OR LONWORKS ENVIRONMENT SUPPORT
  • Provide multiple protocol support for any protocol translation as a full-featured, field-programmable OEM protocol gateway solution
4. MULTI-CLIENT SUPPORT
  • Ensure interoperability between any industrial and/or building automation protocols
5. BACNET COV (CHANGE OF VALUE)
  • Provide fast data communication while reducing traffic over a BACnet network
6. WEB CONFIGURATOR
  • Select the user profile to load multiple configurations
7. ADVANCED AUTO-DISCOVERY
  • Automatically discover known devices on the network and be configured to provide the protocol translation necessar
8. CONFIGURATION AUTO-SELECTOR (VIA DIP SWITCHES)
  • Enable manufacturers to pre-load multiple predefined configurations
9. PROXY TUNNEL
  • An MSA Grid feature that allows users to view the web page on their remote device via the remote FieldServer
10. PROATTACH
  • This FieldServer feature assists users enter valuable site information to enable rich analytics when analyzing or diagnosing data from all sites via the MSA Grid
11. VIRTUAL DATA POINTS
  • A rich Edge Gateway feature that enables manipulation of device data on the FieldServer to produce useful data using a JSON logic engine embedded in the FieldServer Gateway 
Videos
Show More Videos
Show Less Videos
Options
Power Requirements
  • Power: 9-30 VDC or 12-24 VAC
  • RS-422: 15-30 VDC or 12-24 VAC
  • Current draw @ 12 V
    • FPC-C34 @ 12 V = 240 mA
    • FPC-C35 @ 12 V = 250 mA
    • FPC-C36 @ 15 V = 200 mA
    • FPC-C37 @ 15 V = 210 mA
Environment
  • Operating Temperature: -40o to 167oF (-40o to 75oC)
  • Relative Humidity: 5 to 90% RH, non-condensing
Mounting
  • Dimensions (H x W x L): 1.2 x 2.2 x 4.2 in. (3.0 x 5.6 x 10.7 cm)
  • Mounting Holes: Six (6) holes for easy placement
Communications
  • Serial RS-485:
    • Galvanic isolation
    • Baud: 9600, 19200, 38400, 57600, 76800, 115200
  • Ethernet: 
    • 10/100 BaseT
    • MDIX
    • DHCP
BACnet Support (BTL Marked)
  • Alarm and Event notification read properties multiples, and more (see PIC Statement)
  • BACnet COV's, 20,000
  • Support up to 2,000 Host & Field points
  • DIP switches are for setting MAC Address, Node-ID, Baud rate on the RS-485 Field protocol
LonMark Certification on the ProtoCarrier
  • SPID: 80:00:95:46:00:84:04:06
  • Profiles:
    • 0000 – Node object (1)